adstec/irf-modbus-gw

By adstec

•Updated 26 days ago

Modbus RTU (RS-485) to Modbus TCP converter (mbusd) for ADS-TEC IRF3000 industrial firewalls

Image
0

111

adstec/irf-modbus-gw repository overview

⁠Modbus RTU to Modbus TCP Converter for ADS-TEC IRF3000

Sample container by ADS-TEC Industrial IT: the open-source gateway mbusd⁠ in the rootless Docker of the IRF3000 industrial firewalls. Modbus TCP clients (SCADA, HMI, PLC) connect to the IRF on TCP port 502; the gateway forwards the requests to the Modbus RTU slaves on the integrated RS-485 interface.

  • The unit identifier of the Modbus TCP request selects the RTU slave
  • Several clients at the same time, requests are serialized on the bus
  • RS-485 direction switching is handled by the container
  • Exception 0x0B (Gateway Target Device Failed to Respond) if a slave does not answer

⁠Quick start

Enable Access to RS485 under "Configuration > Services > Docker" on the IRF, then:

docker run -d --name modbus-gw --restart unless-stopped \
  --network host --device /dev/ttyS1 \
  -e SERIAL_SPEED=19200 -e SERIAL_MODE=8E1 \
  adstec/irf-modbus-gw
VariableDefaultMeaning
SERIAL_DEVICE/dev/ttyS1RS-485 interface in the container
SERIAL_SPEED19200Baud rate
SERIAL_MODE8E1Data bits, parity (N/E/O), stop bits
TCP_PORT502Modbus TCP port
WAIT_MS500Response timeout per request (ms)
RETRIES3Retries per request
LOG_LEVEL10 errors, 1 warnings, 2 connections

Modbus TCP has no authentication. Restrict the IRF forwarding rule for port 502 to the network of your SCADA/HMI systems and never forward it from a WAN interface. Setup and port forwarding are described in the Docker Application Note of ADS-TEC Industrial IT.

⁠Platforms and license

linux/arm64 (IRF3000), linux/arm/v7. mbusd is licensed under the BSD 3-Clause license.